    Marine HFC-227ea Fire Suppression Plant


    Marine HFC-227ea Fire Suppression Plant

    Description

    The HFC-227e fire extinguishing system has three starting modes: automatic, manual and mechanical emergency operation.

    Because it is colorless, odorless, low-toxic, non-conductive and harmless to object characteristic, HFC-227e is widely used as a fire extinguisher material in important places such as solid surface fires, liquid fires, marine fire-fighting system, offshore oil platform, etc.

    The HFC-227e tank is usually installed in an open and ventilated and away from people workplace. When a fire occurs, the HFC-227e is discharged from the air outlet of the tank, quickly exhausting the oxygen in the place where the fire occurred, and cooling the place where the fire occurred, so as to achieve the purpose of extinguishing the fire.

    Fire-fighting Principle

    Under high temperature conditions, HFC-227ea undergoes physical and chemical reactions, decomposing fluorine-containing free radicals, and interacting with active free radicals such as H+, OH- and other branched chain during the combustion process to interrupt the combustion chain and inhibit the combustion reaction.

    In addition, in the chemical reaction of HFC-227ea, it absorbs a large amount of heat in the gas process can cool and extinguish the fire.

    Technical parameter of marine HFC-227ea fire-fighting system:


    Type

    ZQC-D10/20/30/40/70/90/120/150/180

    start with electronic or local manual way

    ZQC-Q10/20/30/40/70/90/120/150/18O

    start with pneumatic or local manual way

    zQC-T10/20/30/40/70/90/120/150/180

    start with automatic or local manual way

    Filling Density

    ≤1.125Kg/L

    Design Concentration

    8~10%


    Working
    Pressure

    Nominal Working Pressure(MPa )

    2.5/4.2


    Maximum Working Pressure(MPa )

    4.2/5.3


    Cylinder
    Capacity


    HCF-277ea Cylinder(L)

    10/20/30/40/70/90/120/150/180


    Nitrogen Pilot Cylinder(L)

    4


    Spray Time(S)

    ≤10

    Working Temperature Range(℃)

    0~50


    Nominal Working Pressure of Nozzle(MPa )

    10


    Protection Radius of Single Nozzle(m)

    ≤5

    Nozzle protection height (m)

    0.3~5


    Fire Extinguishing Way of System

    Total Flooding

    Location of marine HFC-227ea fire-fighting system: