    Marine Foam Fire-fighting System


    Marine Foam Fire-fighting System

    Description

    Foam proportioning equipment has become more and more popular because of its unparalleled performance. There are two major types of foam proportioning equipment: pressure type foam fire-fighting system and pump balanced type foam fire-fighting system.

    It is widely applied in chemical industrial enterprises, port and dock, large oil storage, airport, oil storage, platform on the sea, etc.

    Principle

    The pressure water enters the tank through the water inlet pipe to generate pressure to squeeze the capsule, so that the foam liquid is extruded through the liquid outlet pipe and automatically mixed with the water in the proportional mixer according to a certain proportion to form a foam mixture liquid to spray foam for fire-fighting.

    Product showcase:

    Marine Foam Fire-fighting System

    Pressure Type Foam proportion Plant

    Pump Balance Type Foam Proportion Plant

    Technical parameter of marine foam fire-fighting system:

    Name

    Pressure Type Foam proportion Plant

    Pump Balance Type Foam Proportion Plant

    Driving type


    The system is operated by water pressure only

    The system is driven by electromotor, diesel engine or water turbine

    Fire extinguishing medium


    Usually use aquecous film-form concentrate

    Any kind of concentrate can be used. Operation without electricity in special occasion can be realized when driven by water turbine and long distance control can be realized when
    use electromotor or diesel engine.

    Pressure Requirement


    There's pressure in foam tank. The tank has pressure
    limitation.

    The foam tank is atmospheric tank. No internal bladder is
    needed. The tank can be made of stainless steel, toughened
    glass, polyethylene and other materials. No pressure requirements. No loss will be caused by bladder damage.

    Location requirements


    Foam tank must be installed in pool or near flow pipe.

    Pump aggregate has no special requirement for installation
    position. It can be arranged according to customers’ needs.

    Proportion accuracy


    The accuracy of the rate of solution can only be
    ensured in a narrow flow range.

    Since equipped with pressure balancing valve, the accuracy of
    the rate of solution can be ensured in a comparatively broad
    flow range.