A60 Ship Pneumatic Fire Damper
1. Features
The fire damper should normal open on getting compressed air&electric power, and should be close on loss of compressed air or electric power. Pneumatic operating pressure is 0.5-0.8MPa;
If the temperature of air in damper duct exceeds 70±3℃, the fusible link if fire damper will be broken and the change valve will cut off the compressed air source to close the fire damper;
On/off status of control electric source for solenoid change valve should be controlled locally or remotely, thus open/close the fire damper;
Manual change valve can be controlled by handle dragline, and the fire damper can close locally or remotely;
on/off signal output when the fire damper is on/off.
2. Types & parameter
|
Control method |
Pneumatic+manual+overtemperature shutdown |
|
Control unit |
Electric actuator |
|
voltage |
AC24-240V, 50/60Hz DC24-125V |
|
Air source |
0.55-0.8 MPa |
|
Installation type |
Bulkhead type/deck type |
|
Fire resistance rating |
A0/A15/A30/A60 |
|
Control mode |
Local/remote/central control |
|
Switch working angle of valve plate |
0°,90° |
|
Switch indication |
Mechanical/remote open or close signal |
|
Turn-off time |
≤2s |
|
Overtemperature shutdown |
70±3℃ |
|
Air-tightness |
Hermetic/non-Hermetic |
|
Air leakage |
Hermetic: meet EN1751: 1998 standard Non-Hermetic: meet CB/T3557-1995 standard |
|
Spindle material |
Stainless steel |
|
Explosion-proof requirement |
Explosion-proof/non-explosion-proof |
|
Level of protection |
IP67 |
|
Valve body color |
Red(standard) or users define |
|
Model |
Hermetic: rectangle/rectangle to round Non-Hermetic: rectangle/round/rectangle to round |


5. IACS Certificate: KR, LR, CCS, CE, DNV▪GL, BV, ABS